당신은 주제를 찾고 있습니까 “altistart 22 scf fault – Troubleshooting StF Fault on Altistart 22 | Schneider Electric Support“? 다음 카테고리의 웹사이트 https://chewathai27.com/you 에서 귀하의 모든 질문에 답변해 드립니다: https://chewathai27.com/you/blog. 바로 아래에서 답을 찾을 수 있습니다. 작성자 Schneider Electric 이(가) 작성한 기사에는 조회수 29,170회 및 좋아요 106개 개의 좋아요가 있습니다.

altistart 22 scf fault 주제에 대한 동영상 보기

여기에서 이 주제에 대한 비디오를 시청하십시오. 주의 깊게 살펴보고 읽고 있는 내용에 대한 피드백을 제공하세요!

d여기에서 Troubleshooting StF Fault on Altistart 22 | Schneider Electric Support – altistart 22 scf fault 주제에 대한 세부정보를 참조하세요

Tutorial for troubleshooting the StF fault code, indicating a longer than expected start-up time, on the Altistart ATS22 soft starter by adjusting the tLS (maximum start time in seconds) and ACC (ramp up time) parameters under the SET menu. tLS must be set higher then the ACC time value.
To learn more, please visit the Schneider Electric FAQ:
http://spr.ly/SchneiderElectricfaqs/FA167393/

altistart 22 scf fault 주제에 대한 자세한 내용은 여기를 참조하세요.

Altistart 22 – Soft start – NET

The following Altistart 22 technical documents are available on the Schneer … If the detected fault persists, contact. Schneer Electric support. SCF.

+ 여기에 자세히 보기

Source: damrexelprod.blob.core.windows.net

Date Published: 7/27/2021

View: 529

altistart 22 scf fault Archives – GeeTech

Home / Products tagged “altistart 22 scf fault”. altistart 22 scf fault. Showing the single result. Default sorting, Sort by popularity, Sort by average …

+ 여기에 자세히 보기

Source: geetech.com.tr

Date Published: 6/6/2021

View: 5755

Altistart 22 Fault Codes Pdf – Fill Online, Printable, Fillable, Blank

Fill Altistart 22 Fault Codes Pdf, Edit online. Sign, fax and printable from … Keywords relevant to altistart 48 ocf fault form. altistart 22 fault codes …

+ 여기에 표시

Source: www.pdffiller.com

Date Published: 9/25/2022

View: 2136

What is an OCF trip code on the ATS22? | FAQs – PRO-FACE

Issue: ATS22 soft starter stopped running. Display is showing OCF. … Resolution: OCF is caused by motor current that exceeds the OId (Overcurrent threshold) and …

+ 여기를 클릭

Source: www.proface.com

Date Published: 12/15/2022

View: 9669

Schneider Electric Altistart 22 | Frequently Asked Questions

What is an OCF trip code on the Altistart 22? OCF is caused by motor current that exceeds the OId (Overcurrent threshold) and OIt (overcurrent time delay) …

+ 여기에 보기

Source: www.mrodrives.com

Date Published: 6/15/2021

View: 3407

How is a fault code cleared or reset, on ATS22?

Needs to clear a fault code, on the ATS22 soft start. Product Line: Altistart 22. Environment: All models … These are InF, trAP, SCF.

+ 여기에 표시

Source: www.pdl.co.nz

Date Published: 4/20/2021

View: 4082

Schneider Electric Altistart 22 Soft Starter – Eltra Trade

Schneer Altistart 22 Soft Starter ✦ Full catalog, Price List: ✓ ATS22 … Internal fault. OCF. Over current. OHF. Overheating of the ATS22 device.

+ 더 읽기

Source: eltra-trade.com

Date Published: 12/30/2022

View: 8088

주제와 관련된 이미지 altistart 22 scf fault

주제와 관련된 더 많은 사진을 참조하십시오 Troubleshooting StF Fault on Altistart 22 | Schneider Electric Support. 댓글에서 더 많은 관련 이미지를 보거나 필요한 경우 더 많은 관련 기사를 볼 수 있습니다.

Troubleshooting StF Fault on Altistart 22 | Schneider Electric Support
Troubleshooting StF Fault on Altistart 22 | Schneider Electric Support

주제에 대한 기사 평가 altistart 22 scf fault

  • Author: Schneider Electric
  • Views: 조회수 29,170회
  • Likes: 좋아요 106개
  • Date Published: 2018. 9. 26.
  • Video Url link: https://www.youtube.com/watch?v=k7ACmivXV7k

What is an OCF trip code on the ATS22?

What is an OCF trip code on the ATS22?

Issue:

ATS22 soft starter stopped running. Display is showing OCF.

Product line:

ATS22, Altistart 22

Environment:

All

Cause:

Motor overcurrent detection

Resolution:

OCF is caused by motor current that exceeds the OId (Overcurrent threshold) and OIt (overcurrent time delay) settings in the PrO menu. The default settings for these from the factory are OId = 200% of the In setting and OIt is 0.5 seconds.

Check that the ATS22 is correctly setup for the application. In should be set at the motor FLA. UIn should be set to the measured Line voltage. Check the setting of ILt under the SEt menu.

For example – if In is set for 100A, the Overcurrent fault would happen when the detected current reaches 200A for 0.5 seconds. OId can be increased to a maximum of 300% of the In value. OIt can be adjusted up to 5.0 seconds maximum.

This function is only active when the ATS22 is in rUn status.

FA291199 | 11-Aug-2020 Print

Schneider Electric Altistart 22 | Frequently Asked Questions

To request a quote for one of the Altistart 22 Soft Starters, please email [email protected] or call 800-691-8511.

How is the Altistart ATS22 set for 3 wire control?

Wire the momentary normally closed STOP contact to LI1 and the momentary normally open START contact to LI2.

Program the ATS22: In the I-O menu, set LI2 to Start (3 wire control).

Why will the Enclosed Altistart 22 product selector not allow selection of Pilot Light Cluster C07?

Shunt Trip Power Circuits B05 ( Basic Shunt Trip ) and S05 ( Full-featured Shunt trip ) are not compatible with Pilot Cluster C07. The Fault indicator pilot on C07 is controlled by the ATS22 trip status relay output. When a shunt trip power circuit is used, the ATS22 trip status relay controls the shunt trip and therefore is not available for pilot light control. In a fault condition, the shunt trip will interrupt power at the main disconnect and all indicator lights will be out.

What causes an StF fault on an Altistart 22 soft starter?

The StF fault means the starter has exceeded the maximum start time setting tLS in the SEt menu.

tLS needs to be set higher then the ACC time. Example: If ACC ramp up time is 10 seconds, set the tLS max starting time to 20 seconds.

If ILt current limit is too low, the motor may not reach full speed within tLS limit.

Mechanical problems on the load may prevent the motor from reaching full speed within tLS limit.

What are the remedies for an Altistart 22 with an OCF over current fault?

Check the values of OId and OIt parameters in PrO menu.

How to set ATS22 to test an unloaded motor?

Testing the ATS with an unloaded motor, usually trips the ATS22 with SSCr. After entering the correct motor data, and set the LAC to ON:

– t90 = Factory 30 but changed to 10. ( Due to No Load connected and monitor ramp acceleration. This value to be changed back or increased when in the field under actual start-up. )

– ILt = Factor 350 changed to 200% for Shop Testing. Value to be changed in the field if Current Limit trips out.

– tLS = Factory 15s changed to 60s for Shop Testing. ( Changed back to 15s after completion of testing. )

– ACC = Factory 10s change to 60s for Shop Testing. ( Changed back to 10s after completion of testing. )

– SSC = Factory On, changed to oFF. ( Using Voltage control vs. Torque. )

– ItH = Found to be on ErUn, changed to On. ( Factory is On. )

How is a faulted ATS22 reset?

After the condition that created the fault has been corrected, a fault reset can be accomplished several ways:

1) Remove control power from CL1-CL2. After the display has gone blank, apply control power.

2) On the integral or remote keypad, press the 3-key combination of ENT / UP arrow / DOWN arrow, simultaneously.

3) Wire a reset contact to logic input LI2 or LI3 and program it to rSt (remote reset). A momentary contact closure will reset.

4) Use Modbus command word 752 and write a 1 to bit 3

What is NRDY status on the ATS22 soft starter?

nrdY means not ready. Description is a stop command is present, with line and control power on.

or Main power is switching off.

LI1=0 and LI2= 1 in 2 wire control

LI1=1 and LI2= 1 in 3 wire control at power up

Does the Altistart 22 have an analog output?

No, there is not an analog output feature on the ATS22.

What can cause a PHF (phase fault) on the ATS22 Soft Start?

Loss of a line phase.

1. Check the line voltage, the connection to the soft starter and any isolating devices located between the line and the soft starter (contactors, fuses, circuit breakers, etc.).

2. Check the motor connection and any isolating devices located between the soft starter and the motor (contactors, circuit breakers, etc.).

3. Check the motor state.

4. Verify that the run command to the ATS22 is applied AFTER the supply power is applied to L1L2L3. If an isolation contactor coil is energized at the same time as a run command on LI2, expect that the run command will become active before the supply power is applied. The ATS22 will attempt to start, but see no amperage. The PHF fault will follow immediately.

What is the PHbd fault on the ATS22 soft starter?

PHbd is a phase unbalance fault.

1. Check line voltage (Phase to phase the voltage should be balanced)

2. PRO Menu check the following values Ubt and Ubd

a. Ubd – Unbalance threshold (trips the soft start in case of motor current imbalance between 2 or 3 phases. The value is Con % of IN in the COnF menu. This setting can be disabled.

b. Ubt – Unbalance time delay ( Time delay before the PHbd fault is taken into account if there is a current imbalance equal to or greater than Ubd.)

3. With Ubd turned off, run the motor and check the current draw on each phase ( check input and output currents. Between the three phases the current should be balanced. If the current is not balanced and the voltage is balanced problem is related to the motor. If both are balanced, then the problem could be related to the soft start.

What can cause an INF fault on the Altistart 22 soft starter?

Try cycling on and off CL1 and CL2 to see if the fault clears.

If the fault remains, you will need to contact the drives product support group.

Can a reversing contactor be used with an Altistart 22?

Yes, it is possible to use a reversing contactor with ATS22.

How can you change the relay configuration on an ATS22?

First open access to the IO menu by going to the ConF menu, set LAC = ON.

Then go to the IO menu ad set r1 or r2 to the appropriate configuration.

What causes USF on an ATS22 series soft starter?

USF is an Undervoltage Fault. Basically, the incoming supply voltage is too low. The following parameters affect the USF fault:

In the ConF menu, parameter UIn should be set to the nominal incoming 3 phase voltage. The factory default is 480V.

In the PrO menu, parameter USd ( Under Voltage Threshold ) sets the threshold as a percentage of parameter UIn. Parameter USt (Under Voltage Time Delay ) sets the amount of time delay in seconds until a USF trip. The voltage must remain under the threshold for the entire delay to activate the fault.

Note that the undervoltage protection feature becomes operational only after a run command has been issued. When voltage drops to zero, the soft starter will trip immediately, overriding the time delay.

How to increase the starting torque on the ATS22?

Increasing the parameters below can aid in providing more breakaway torque to get the motor moving and up to speed.

SET Menu

Parameter T90 – Initial Voltage. This value is adjustable from 10% to 50% of the full voltage, in increments of 5%. Factory setting is 30%.

Paramter ILt – Current limit. This is the maximum current allowed during the startup. It is adjustable up to 700% of the Motor Rated Current (In parameter). The maximum value is 350% of the Softstart rated current (IcL parameter). Factory setting is 350%.

ADJ Menu (To access the ADJ menu, LAC parameter under the SET menu must be set to “on”)

Parameter bSt – Boost Time. This provides an 80% pulse of the Line voltage (UIn parameter) for 0.0 to 1.0 seconds. Factory setting is 0.0.

What is an OCF trip code on the Altistart 22?

OCF is caused by motor current that exceeds the OId (Overcurrent threshold) and OIt (overcurrent time delay) settings in the PrO menu. The default settings for these from the factory are OId = 200% of the In setting and OIt is 0.5 seconds.

Check that the ATS22 is correctly setup for the application. In should be set at the motor FLA. UIn should be set to the measured Line voltage. Check the setting of ILt under the SEt menu.

Will the ATS22 display light up with control voltage only?

Yes, the HMI should light with control voltage applied. If the display does not light up:

Disconnect the remote HMI.

Verify the correct control voltage is measured at the ATS22 terminals CL1 and CL2

For models ATS22…S6 and ATS22…Q the control voltage should measure ~230vac

For models ATS22…S6U the control voltage should measure ~110vac

How can you view the Altistart 22 soft starters fault history?

SUP menu

Find dEF1= Tip history 1 thru dEF9 Trip history 9

Can you run an Altistart 22 softstart on an ungrounded Delta system?

Yes, the ATS22 can be used on an ungrounded delta system as long as the line voltages are balanced phase to phase (L1, L2 and L3).

What is the max current rating of an ATS22 relay?

Max switching capability:

5A – 250VAC or 30VDC on resistive load (p.f.=1)

2A – 250VAC or 30VDC on inductive load (p.f=0.4)

What causes a CONE fault code on an ATS22 softstart?

This is caused by a loss of communication on the Rj45 port.

If there is an external keypad used please make sure that the cable is connected to the RJ45 port on the softstart.

Can parameters be locked or password protected on ATS22 Softstart?

There is no password protection in ATS22. However, Cod parameter can be used to Lock or Unlock the parameters.

It is used to enable or disable parameters modification on the displays.

When not locked: all R/W parameters can be modified. Also accessible with key combination (ESC + UP +Down) arrow keys

When locked: all parameters are read only on local display or remote keypad display (the parameters can be still modified by serial link and SoMove software).

Can File Transfer be done in Altistart 22 using Remote Keypad?

No. File transfer cannot be done with Remote Keypad. Need SoMove Software or Multiloader for that purpose.

What causes an A17 fault on the ATS22 soft starter?

Keypad buttons are being held longer than 10 seconds. Try releasing the touch screen buttons. Do not hold them more than 10 seconds. Try swapping out the remote HMI keypad. See if the problem follows the keypad or stays with the soft starter.

To reset the fault you have to power cycle the soft starter.

Does the ATS22 soft starters come with built in overload protection?

Yes, The ATS22 soft starters have built in overload protection. The default motor thermal protection is IEC class 10.

You can adjust this value in the programming in the SEt menu.

Do the Altistart 22 soft starters have a internal shorting bypass contactor?

Yes. It is a shorting contactor that closes when the motor is up to full speed. The purpose is to give the current a path around the SCRs. This prolongs the life of the SCRs and reduces heat produced by the soft starter.

Note that this contactor is not for full voltage across the line starting without the soft starter.

What is the command word for the Altistart 22 soft starters for network communication?

The command word address for the ATS22 soft starter is 752.

The ETA status word address for the ATS22 soft starter is 256.

What does an OLF fault code mean on the ATS22 soft starters?

OLF means motor overload fault. To reset the fault you can go into the Pro menu find ITH set this to OFF power cycle then set it to ON. This will reset the OLF fault now. Otherwise you have to wait for it to time out and reset on its own. Next, check the motor for blockage, phase rotation etc. Then, check the ACC and tHP settings in SET menu, if ACC= 10 seconds or more, try adjusting the tHP to class 20 or class 30.

What would cause the trip LED to flash on an ATS22 Softstart?

Trip LED on = trip with immediate stop.

Trip LED OFF= no problem

Trip LED flashing = alarm warning no-stop.

If the LEDs are flashing please consult your ATS22 manual and look at the possible alarm conditions.

How is a fault code cleared or reset, on ATS22?

FA241674

08 April 2022

Needs to clear a fault code, on the ATS22 soft start.Altistart 22All modelsThe fault code must be cleared to make ATS22 functional.After the condition that created the fault has been corrected, a fault reset can be accomplished several ways:1) Remove control power from CL1-CL2. After the display has gone blank, apply control power.2) On the integral or remote keypad, press the 3-key combination of ENT / UP arrow / DOWN arrow, simultaneously.3) Wire a reset contact to logic input LI2 or LI3 and program it to rSt (remote reset). A momentary contact closure will reset.4) Use Modbus command word 752 and write a 1 to bit 3Note that several fault codes require method 1) above. These are InF, trAP, SCF.

ATS22 Soft Starter, Schneider Altistart 22

The Schneider Electric Altistart 22 is a device that provides a soft start and stops of three-phase asynchronous electric motors by controlling the change in voltage and torque. It is used for three-phase asynchronous electric motors with a squirrel-cage rotor from 4 to 400 kW.

This line of soft starter consists of two product lines:

Three-phase mains voltage from 230 to 440V, 50/60 Hz (ATS 22···Q).

Three-phase supply voltage from 208 to 600 V, 50/60 Hz (ATS 22···S6 and ATS 22···S6U).

ATS22 soft starters and soft brakes are pre-programmed for normal use with motor protection class 10.

Altistart 22 models have been designed for applications where the most important requirements are:

reliability;

safety of service personnel and equipment;

ease of commissioning and maintenance.

The device provides thermal protection of the electric motor, makes it easy to control the parameters of the mechanism and, thanks to the SoMove software, can be put into operation immediately after installation.

The bypass function, based on the use of a bypass contactor inside the device, allows the Altistart 22 – ATS22 to be used for applications that require a bypass contactor at the end of the starting process, for example, to reduce heat dissipation by the starting device itself.

Thanks to the built-in terminal in the Altistart 22 – ATS22 device, the user can both configure and adjust parameters, and control their value to check the compliance of the mechanism with the underlying algorithm.

How to wire the Schneider Altistart 22?

When connecting soft starter Schneider altistart 22, separate laying of control circuits and power (power and load) circuits is required. The power cable for supplying power to the motor must be located as far as possible from other power circuits, they should not be laid in the same cable duct. This separation reduces the likelihood of electromagnetic interference in control circuits.

When mounting the ATS22, observe the following requirements:

The voltage and frequency parameters of the supply network must correspond to the characteristics of the ATS22 device

A disconnector must be installed between the main supply and the ATS2.

If a line contactor is used as an isolating device, it must be switched on before or simultaneously with the start command. If there is no voltage at the power terminals L1, L2, and L3 of the ATS22 within 500 ms after the start command is given, a PHF trip occurs.

External overcurrent protection devices (OCPD), fuses, or circuit breakers must be installed on the mains side of the ATS22.

Capacitive power factor correction devices cannot be connected to the motor controlled by the ATS22. If power factor correction is required, capacitor banks can be installed on the side of the main. A separate contractor must be used to disconnect the capacitor bank when the motor is stopped or during acceleration and deceleration.

Softstarter uses power semiconductors to control the motor. When checking the condition of cable runs or motor insulation, do not connect insulation resistance measuring devices or high voltage insulation resistance test equipment to the ATS22, as the test voltage may damage it. Always disconnect the device from the power cables or the motor before starting these checks.

The ATS22 contains electronic monitoring circuits that monitor the state of the power semiconductors.

Since solid-state power cells may not be able to completely cut off power to the motor in the event of a failure of the ATS22, an additional isolating device is required on the side of the main. Either a shunt trip circuit breaker or a contactor can be used for this purpose. The isolation device is controlled by the device fault relay ATS22. When a fault occurs, this relay opens its contact, which leads to a guaranteed shutdown of the isolation device and the interruption of the power supply to the starting device and the motor. The characteristics of the isolation device must be such that the motor current can be interrupted when the rotor is locked.

Schneider Altistart 22 fault codes

Let’s look at fault codes of Altistart 22 Telemecanique.

Error code Description bPF Bypass contactor fault CFF Incorrect configuration on power-up EtF External fault GrdF Leakage current trip InF Internal fault OCF Over current OHF Overheating of the ATS22 device OLF Motor overload OSF High voltage OtF Motor overheating is detected by sensors PTC PHbd Phase asymmetry PHF Phase failure (mains or motor side) Mains frequency out of range Protection function configured in the PrO menu PIF Phase rotation. The phase sequence does not match the one configured by the PHr parameter in the PrO menu trAP Interrupt code SCF Short circuit at the output of the ATS22 device SLF Modbus timeout SnbF Too many starts SSCr Thyristor short circuit or incorrect connection StF Error: start time mismatch, delayed start tbS Too many starts UCF Current underload USF Low voltage or no voltage

As well as the errors of the Altistart 22 soft starter displayed on the display of the remote terminal.

Message Description Add. information InIt Initialization Initializing the microcontroller Finding the connection configuration COME Lost connection Timeout 50ms Message appears after 20 connection attempts A-17 Incorrect key operation Key pressed continuously for more than 10 seconds

Open membrane switch

The terminal is in the initialization state and the key has already been pressed CLr Confirm Fault Reset The message appears if: The STOP button has been pressed while the ATS22 has tripped on an alarm dEUE Non-compliance with ATS22 Type mismatch between the remote terminal and connected device rOME ROM failure Remote terminal ROM failure rAME RAM failure Remote terminal RAM failure CPUE Processor failure Remote terminal processor failure

If you need more information, you can always study the Schneider electric Altistart 22 manual.

We offer full model range of this series. If you need to buy it at the profitable price contact our managers.

키워드에 대한 정보 altistart 22 scf fault

다음은 Bing에서 altistart 22 scf fault 주제에 대한 검색 결과입니다. 필요한 경우 더 읽을 수 있습니다.

이 기사는 인터넷의 다양한 출처에서 편집되었습니다. 이 기사가 유용했기를 바랍니다. 이 기사가 유용하다고 생각되면 공유하십시오. 매우 감사합니다!

사람들이 주제에 대해 자주 검색하는 키워드 Troubleshooting StF Fault on Altistart 22 | Schneider Electric Support

  • 동영상
  • 공유
  • 카메라폰
  • 동영상폰
  • 무료
  • 올리기

Troubleshooting #StF #Fault #on #Altistart #22 #| #Schneider #Electric #Support


YouTube에서 altistart 22 scf fault 주제의 다른 동영상 보기

주제에 대한 기사를 시청해 주셔서 감사합니다 Troubleshooting StF Fault on Altistart 22 | Schneider Electric Support | altistart 22 scf fault, 이 기사가 유용하다고 생각되면 공유하십시오, 매우 감사합니다.

Leave a Comment